Convert AWG to mm².
Accepts AWG numbers (e.g. 12) and the special 1/0, 2/0, 3/0, 4/0 sizes.
To convert AWG to mm², use the standardized wire-gauge formula — AWG steps are non-linear, so each gauge maps to a specific cross-section.
American Wire Gauge to metric cross-sectional area — formula, reference values, and a live converter.
AWG is a logarithmic sizing scale: each step is a fixed ratio in diameter, not a fixed step in area.
Smaller AWG number means thicker wire. Sizes larger than 1 AWG are written 1/0 (one aught), 2/0, up to 4/0.
Formula
d (mm) = 0.127 × 92^((36 − n) / 39) A (mm²) = π × (d / 2)² n = AWG number (use n = −3 for 4/0, n = −2 for 3/0, n = −1 for 2/0, n = 0 for 1/0)
Per ASTM B258. The 0.127 mm coefficient is 0.005 inch × 25.4. The formula gives the bare-conductor diameter; cross-sectional area is computed from that.
Reference values
| AWG | Diameter (mm) | Area (mm²) | Next IEC standard size up (mm²) |
|---|---|---|---|
| 4/0 | 11.684 | 107.22 | 120 |
| 3/0 | 10.405 | 85.03 | 95 |
| 2/0 | 9.266 | 67.43 | 70 |
| 1/0 | 8.251 | 53.48 | 70 |
| 1 | 7.348 | 42.41 | 50 |
| 2 | 6.544 | 33.63 | 35 |
| 4 | 5.189 | 21.15 | 25 |
| 6 | 4.115 | 13.30 | 16 |
| 8 | 3.264 | 8.37 | 10 |
| 10 | 2.588 | 5.26 | 6 |
| 12 | 2.053 | 3.31 | 4 |
| 14 | 1.628 | 2.08 | 2.5 |
| 16 | 1.291 | 1.31 | 1.5 |
| 18 | 1.024 | 0.823 | 1.0 |
| 20 | 0.812 | 0.518 | 0.75 |
| 22 | 0.644 | 0.326 | 0.5 |
| 24 | 0.511 | 0.205 | 0.5 (smaller IEC sizes are non-standard) |
| 26 | 0.405 | 0.129 | — |
| 28 | 0.321 | 0.0810 | — |
| 30 | 0.255 | 0.0509 | — |
| 32 | 0.202 | 0.0320 | — |
| 34 | 0.160 | 0.0201 | — |
| 36 | 0.127 | 0.0127 | — |
| 40 | 0.0799 | 0.00501 | — |
"Next IEC standard size up" is the next-larger size in IEC 60228 (the standard for conductors of insulated cables): 0.5, 0.75, 1.0, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120, 150, 185, 240 mm². When sourcing in metric to replace AWG, round UP — never down — to maintain ampacity. For AWG sizes below 0.5 mm², IEC 60228 does not define a standard size; specify by mm² directly.
Things to watch for
- AWG ≠ standard metric. The IEC standard sizes (1.5, 2.5, 4, 6, 10, 16 mm² ...) don't align exactly with any AWG size. 14 AWG is 2.08 mm² but you'll usually order 2.5 mm² in metric — the next standard size up.
- Round up when substituting. If you're replacing AWG wire with metric in an existing design, the metric wire must be at least as large in cross-section. Rounding down can violate ampacity.
- NEC and IEC ampacity differ. The same physical wire has different rated ampacity under NEC vs IEC because the calculation method, ambient temperature reference, and installation assumptions differ. Always size to the local code's tables, not by direct cross-reference.
- Stranded wire has lower effective area. A stranded conductor of nominal 2.5 mm² area uses smaller strands with gaps, so its actual copper area is slightly less than a solid 2.5 mm². For low-voltage signal wiring this doesn't matter; for high-current power runs, check the manufacturer datasheet.
- 4/0 is roughly 107 mm² but not equal to it. The closest IEC standard is 120 mm². For very large feeders, you'll often see both expressed (e.g. "750 kcmil = ~380 mm²").
What is a American Wire Gauge?
AWG is a logarithmic wire-size scale defined by ASTM B258. The diameter formula is d = 0.005 × 92^((36−n)/39) in. Smaller AWG numbers mean thicker wire. Electrical wire sizing in the US, Canada, and parts of Latin America.
What is a square millimeter?
A unit of cross-sectional area equal to one millimeter by one millimeter, used to specify wire conductor size in IEC standards. Electrical wire sizing in most countries outside North America, per IEC 60228.
How to convert American Wire Gauge to square millimeter
To convert a value from American Wire Gauge (AWG) to square millimeter (mm²), apply the conversion factor shown in the formula above. The calculation is the same whether you do it by hand, in a spreadsheet, or with the live converter on this page.
Steps:
- Take your input value in AWG.
- Apply the formula
d (mm) = 0.127 × 92^((36 − n) / 39) A (mm²) = π × (d / 2)² n = AWG number (use n = −3 for 4/0, n = −2 for 3/0, n = −1 for 2/0, n = 0 for 1/0). - The result is your value in mm².
For repeated calculations, save the formula in a spreadsheet or use the live converter at the top of this page — it handles the math automatically and displays the result as you type.
Frequently asked questions
How do I convert AWG to mm²?
AWG to mm² uses the ASTM B258 formula: diameter d = 0.127 mm × 92^((36 − n)/39), then area = π/4 × d². Example: 12 AWG = 3.31 mm² and 10 AWG = 5.26 mm². Metric wire comes in fixed sizes (1.5, 2.5, 4, 6 mm²…), so pick the next larger standard size.
Which is bigger, AWG or mm²?
The scales run in opposite directions. A larger AWG number means a thinner wire. A larger mm² value means a thicker wire.
When would I use AWG versus mm²?
Use AWG for US wire sizes. Use mm² for wire sizes outside North America. Convert when a specification, label or manual uses the other unit.
How precise is this AWG to mm² conversion?
The converter applies the ASTM B258 formula exactly. Real wire is made in fixed sizes, so always round up to the next standard size.
Is the conversion ratio exact, or an approximation?
The AWG formula is exact, but AWG sizes are discrete and metric wire sizes are discrete. A conversion gives the nearest equivalent, not an identical wire.
Sources & verification
Unit definitions used by this converter:
- American Wire Gauge (AWG): diameter d = 0.127 mm × 92(36 − n)/39, area = π/4 × d², from ASTM B258. The standard is sold by ASTM and was not checked directly; the formula's results match the AWG table on this page.
- square millimeter: 1 mm² = 1 × 10−6 m², exact — BIPM SI Brochure, 9th ed.
Related conversions
mm² → AWG (closest)
Convert mm² to AWG.
acre → ha
Convert acre to hectare.
acre → m²
Convert acre to square meter.
ft² → m²
Convert square foot to square meter.
ha → acre
Convert hectare to acre.
m² → acre
Convert square meter to acre.
See also
mm² → AWG
Convert the other direction — metric cross-section to AWG.
AWG cheat sheet
Complete AWG reference with NEC ampacity, resistance per length, and diameters.
Guide: AWG vs metric
Why "smaller number = bigger wire", and the gotchas when sourcing internationally.
Wire gauge calculator
Pick the right AWG given amperage, run length, and voltage drop.
All unit conversions
Every converter on the site, grouped by category.