Electrical · Guide

AWG vs metric wire sizing.

Why "smaller number = bigger wire" makes sense once you know the history, how AWG relates to mm², and the gotchas when sourcing internationally.

TL;DR

AWG is a logarithmic US wire sizing system where larger numbers mean smaller wires — a relic of counting wire-drawing operations. To cross-reference with metric: 14 AWG ≈ 2.5 mm², 12 AWG ≈ 4 mm², 10 AWG ≈ 6 mm², 8 AWG ≈ 10 mm². When sourcing internationally, round up to the next metric size. Always size to the local code's ampacity tables — NEC and IEC use different methodology.

The American Wire Gauge in one paragraph

AWG is a US-developed wire sizing system where each "gauge number" corresponds to a specific diameter. The system runs from 4/0 (read "four-aught," the thickest in common use) down to 40 and beyond (the thinnest). Each gauge step is a constant ratio in diameter — about 0.890× per step — which means the area changes by a factor of 2 every three gauge numbers. This logarithmic spacing is the system's main quirk and the source of most confusion.

"Smaller number, bigger wire" — and why

AWG numbers count down as wire gets thicker. 14 AWG is a typical residential branch circuit wire (about 1.6 mm diameter). 8 AWG is much thicker (3.3 mm). 1 AWG is bigger still. After 1 AWG comes 1/0 ("one-aught"), then 2/0, 3/0, 4/0. This is the opposite of metric wire, where the number IS the cross-sectional area in mm² — so a 6 mm² wire is bigger than a 1.5 mm² wire, exactly as you'd expect.

The reason for the inverted numbering is historical. AWG was originally defined by how many times a wire was drawn through a die to make it thinner — each "draw" reduced the diameter. A "20-gauge" wire had been drawn 20 times; a "1-gauge" wire only once. The actual draw-count meaning disappeared long ago, but the inverted numbering survived.

The conversion isn't a simple ratio

Because AWG is logarithmic in diameter and metric mm² is linear in area, the relationship between them is logarithmic, not proportional. There's no constant factor like "1 inch = 2.54 cm." Instead:

d(n) in inches = 0.005 × 92^((36 − n) / 39)

Where n is the AWG number (with 1/0, 2/0, 3/0, 4/0 treated as 0, −1, −2, −3). From the diameter, the metric area in mm² is π × (d/2)². This formula is the official ASTM B258 definition.

The cross-reference you actually need

Memorize these closest matches — they cover 95% of practical work:

AWGApprox mm²Closest metricCommon use
14 AWG2.08 mm²2.5 mm²15 A residential circuits
12 AWG3.31 mm²4 mm²20 A residential circuits
10 AWG5.26 mm²6 mm²30 A dryer / appliance circuits
8 AWG8.37 mm²10 mm²40-50 A range circuits
6 AWG13.3 mm²16 mm²55-65 A subpanel feeds
4 AWG21.2 mm²25 mm²70-85 A feeds
2 AWG33.6 mm²35 mm²95-115 A service entrances
1/0 AWG53.5 mm²50 mm²125-150 A service
4/0 AWG107.2 mm²120 mm²195-230 A main service

Note that the metric sizes don't exactly match AWG — they're "close enough" rather than identical. The metric series rounds to convenient values (1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 120 mm²). When you're sourcing a 12 AWG cable in a metric country, you'd typically buy 4 mm² — slightly larger than the AWG spec, which is fine, but slightly more expensive.

The ampacity question

Wire size doesn't determine current capacity alone. Insulation type, ambient temperature, conduit fill, and conductor count all matter. In the US, the NEC's Table 310.16 is the authority. In Europe, the equivalent is IEC 60364-5-52. The two standards use different methodology and don't always agree.

A typical example: 2.5 mm² European cable (close to 14 AWG) is rated for 24-27 A in a typical installation per IEC; 14 AWG in the US is rated for 15-20 A per NEC (with §240.4(D) limiting to 15 A regardless of insulation). The European rating isn't "wrong" — it's based on different assumed installation conditions (ambient temperature, bundling, length). Always size to the standard in your jurisdiction.

When you have to source internationally

Three concrete situations come up frequently:

Buying a European appliance for a US installation

The appliance comes with metric cable. If the cable terminates in a plug for the local market, you can usually replace the plug with a US one and proceed. If the cable enters the wall, you need a junction transition: terminate the metric cable in a junction box, splice to AWG using listed connectors, and run AWG to the panel. Most jurisdictions require the AWG portion to comply with NEC.

Buying US wire for export

Round up the metric size. 14 AWG → 2.5 mm² (the AWG is 2.08 mm²; the metric is 2.5 mm², slightly bigger). 12 AWG → 4 mm². 10 AWG → 6 mm². The metric wire will safely handle the same or higher current; the cost increase is modest.

Reading a Chinese or Korean spec sheet

Asian electronics specs are usually metric. A "0.5 mm²" stranded wire in a Chinese spec is about 20 AWG. A "0.75 mm²" wire is about 18 AWG. These tiny gauges are common in flexible cords and appliance cables. Use our AWG cheat sheet for the full cross-reference.

The SWG trap

One more historical wire-sizing system you may run into is SWG — Standard Wire Gauge, originally British, used in some older equipment and still occasionally specified in industries with British heritage (rail, certain types of fasteners, music wire). SWG numbers look similar to AWG numbers but the actual diameters differ. A 16 SWG wire is 1.626 mm; a 16 AWG wire is 1.291 mm. Don't substitute without checking — they're meaningfully different.

Common pitfalls

Sources & further reading

Related on unitcheatsheet.com