Electrical · Cheat sheet

AWG wire gauge chart.

→ Pick a property and enter a value.

For copper building wire, use 14 AWG for a 15 A circuit, 12 AWG for 20 A and 10 AWG for 30 A. These are the maximum breaker sizes in NEC 240.4(D). At 60 °C, 8 AWG carries 40 A and 6 AWG carries 55 A. A long run can need a larger wire to limit voltage drop.

Diameter, area, resistance, and ampacity for every common AWG size — from 4/0 down to 30. Sourced from ASTM B258 (geometry) and NEC Table 310.16 (ampacity).

↓ PDF → Sizing calculator

Next step AWG vs metric wire sizing — Metric mm² equivalents

The chart

↔ swipe to see all columns on mobile
AWG Diameter Area Resistance
Ω / 1000 ft @ 20 °C
Ampacity (NEC, Cu, 30 °C amb.)
in mm mm² kcmil 60 °C 75 °C 90 °C
4/00.4611.68107.2211.60.04901195230260
3/00.409610.485.03167.80.0618165200225
2/00.36489.26667.43133.10.07793145175195
1/00.32498.25153.48105.50.09827125150170
10.28937.34842.4183.690.1239110130145
20.25766.54433.6366.370.156395115130
30.22945.82726.6752.630.19785100115
40.20435.18921.1541.740.2485708595
50.18194.62116.7733.10.3133———
60.1624.11513.326.250.3951556575
70.14433.66510.5520.820.4982———
80.12853.2648.36616.510.6282405055
90.11442.9066.63413.090.7921———
100.10192.5885.26110.380.9988303540
110.090742.3054.1728.2341.26———
120.080812.0533.3096.531.588202530
130.071961.8282.6245.1782.003———
140.064081.6282.0814.1072.525152025
160.050821.2911.3092.5834.015———
180.04031.0240.8231.6246.385———
200.031960.81180.51761.02210.15———
220.025350.64380.32550.642416.14———
240.02010.51060.20470.40425.67———
260.015940.40490.12880.254140.81———
280.012640.32110.080980.159864.9———
300.010030.25460.050930.1005103.2———

Ampacity notes. Values are for copper conductors, not more than three current-carrying conductors in a raceway, at 30 °C ambient. The temperature column refers to the conductor insulation rating (TW = 60 °C, THW/RHW = 75 °C, THHN/XHHW = 90 °C). Derating factors apply for higher ambient temperatures or more conductors — see NEC §310.15(B). Aluminum is different; reduce by roughly one column (e.g., 10 AWG Al ampacity ≈ 12 AWG Cu).

Common applications

Practical wire gauges by use case. These are typical residential / light-commercial pairings, not a substitute for the NEC or your local code.

Use caseTypical AWGWhy
Lamp / fixture wiring18, 16Low current (under 10 A), flexibility matters
Doorbells, thermostats18, 20Class 2 signaling, very low current
15 A receptacles, lighting14Minimum for 15 A breaker per NEC
20 A kitchen / bath circuits12Minimum for 20 A breaker per NEC
Electric dryer (30 A)1030 A circuit @ 240 V
Electric range (40–50 A)8, 6Sized to breaker; 6 AWG common for 50 A
Subpanel feed (100 A)3, 22 AWG Cu @ 75 °C insulation
Main service entrance (200 A)2/0, 3/02/0 AWG Cu or 4/0 Al per NEC 310.12
USB cable (data)28USB 2.0 spec; thicker pairs (24) for power
Speaker wire (typical run)16, 1414 AWG for runs over 50 ft to keep loss low

Common pitfalls

AWG wire gauge chart: page 1 of the printable PDF
Page 1 of the printable AWG wire gauge chart PDF. Select the image to download the full chart.

Common questions

Why does smaller AWG mean thicker wire?

AWG was originally based on the number of times a wire was drawn through progressively smaller dies — each pass made the wire thinner. So a 30-gauge wire was drawn 30 times (very thin), while 1-gauge was drawn only once (very thick). The number counts process steps, not size.

How do I size a wire for a 50-amp circuit?

Per NEC Table 310.16, 6 AWG copper at 75°C is rated 65 A and is the standard for a 50-amp circuit (NEC 80% derating rule: 65 × 0.8 = 52 A continuous). For aluminum, you'd step up to 4 AWG. Always check the specific code edition, the temperature rating of your terminals (60°C, 75°C, or 90°C), and the run length for voltage drop on long runs.

Is 12 AWG enough for 20 amps?

Yes, by NEC. 12 AWG copper has a 25 A ampacity at 60°C terminations and 30 A at 75°C, so a 20 A breaker is well within limit. The 80% continuous-load rule means it's actually rated for 24 A continuous at 60°C — comfortably above 20 A. Just confirm your terminations match the wire's temperature class.

What's the voltage drop on a 100-foot 12 AWG run?

For a 20 A load on 120 V at 100 ft round-trip (so 50 ft each way), 12 AWG copper has about 0.16 Ω resistance for the round trip. Voltage drop = 20 A × 0.16 Ω = 3.2 V, or 2.7%. NEC recommends keeping branch-circuit drop under 3%, so 12 AWG at 100 ft is right at the edge — bump to 10 AWG for longer runs or higher loads.

Can I run 14 AWG on a 20-amp breaker?

No. NEC requires 14 AWG to be on a maximum 15 A breaker, 12 AWG on max 20 A, and 10 AWG on max 30 A. The breaker protects the wire — if the breaker is rated higher than the wire ampacity, an overload won't trip the breaker before the wire heats. This is a fire hazard and a code violation.

Sources

  • Geometry (diameter, area): ASTM B258 — Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors. Diameters computed from the formula d(n) = 0.005 × 92^((36−n)/39) inches.
  • Resistance: Based on resistivity of annealed copper (1.7241 × 10⁻⁸ Ω·m at 20 °C, IEC 60228). Values given are for solid copper; stranded conductors are typically 2–4% higher.
  • Ampacity: NFPA 70 (National Electrical Code), Table 310.16 — Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts. Values apply to copper conductors, not more than three current-carrying conductors in a raceway, at 30 °C ambient.
  • Breaker limits for small conductors: NFPA 70 (NEC), Section 240.4(D) — overcurrent protection is limited to 15 A for 14 AWG copper, 20 A for 12 AWG and 30 A for 10 AWG.

Last content change: 6 November 2026 · Changelog

Disclaimer. This chart is provided for reference and educational use. Electrical installations must comply with the NEC and local codes; consult a licensed electrician for any installation you're not qualified to perform.

See also